ZAXDP31 Differential Pressure Transmitter-Basic

The ZAXDP series intelligent pressure/differential pressure transmitters feature a central sensing unit utilizing advanced high-precision silicon pressure and differential pressure sensor technology. The sensors are positioned at the top of the metal housing, maintaining mechanical and thermal isolation from the medium contact surface. Integrated glass-sintered sensor leads ensure robust electrical insulation from the metal substrate, enhancing circuit flexibility and transient voltage protection capabilities. With platinum-grade accuracy of ±0.05% and unidirectional overpressure capacity up to 25MPa, the transmitters demonstrate exceptional static pressure performance. Their static pressure error is optimally controlled within ±0.05%/10MPa, while temperature influence remains minimal at ±0.04%/10K.

ZAX single crystall pressure transmitter Manual

Apply to All ZAX single crystall pressure transmitter instruction

Pending Update

Pending Update

  • Gas
  • Vapour 
  • Liquid
  • ±0.05%, ±0.075%, ±0. 1% (including linearity, hysteresis, and repeatability from zero)

  • ±0. 1%/3 years

  • ≤±0.04%URL/10

  • ±0.05%/10MPa

  • 10 to 36V DC (recommended 24V DC)

  • ±0.001% /10V (10-36V DC), negligible

  • When TD> 10 (where TD = maximum range/ adjustment range), the output accuracy is ±(0.075 × TD)%. The square root output accuracy is 1.5 times of the aforementioned linear reference accuracy.

  • -40~ 85

  • -40℃ ~ 120℃
  • -40~ 105

  • LCD, OLED

  • : -20to 70(LCD) and-40to 80(OLED)

  • M20*1.5
  • -0.1 to 0.3MPa
  • Please select a range code within rated range. Adjustable range within rated range

  • The zero point and range can be adjusted to any value within the measurement range of the meter, provided that the calibrated range is greater than or equal to the minimum range.

  • Keep installation position perpendicular to the diaphragm do not cause zero drift. However, if the installation position deviates from the diaphragm by more than 90°, a zero drift of <0.4kPa may occur. It can be corrected by adjusting the zero point and no effect to full range measurement.

  • Two-wire 4-20mA HART system compliant with NAMIR NE43 standards, linear or square root output are optional.

  • Imin=3.9mA ,Imax=21.0mA

  • If the sensor or circuit fails, The automatic diagnostic function outputs 3.9 or 21 mA.

  • Low mA mode: 3.9 mA/High mA mode:21mA. Default mode:High mA mode

  • The amplifier component has a damping constant of 0.1s; the sensor’s response time constant ranges from 0.1 to 1.6 s, depending on the range and range ratio. Additional adjustable response time constant is available from 0 to 100s.

  • <15s

xxxxx

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.